ULTRACAP is a DC UPS based on ultracapacitor technology. Provide energy to the control system in the time between power failures and initiation of backup power systems, such as diesel generators or fuel cells. It is used in sectors where continuity of service is required such as process industry and data centers.
Thanks to the long life and high capacity ultracapacitor technology, no maintenance is required.
It doesn't require the use of batteries, reducing the size and weight.
| TECHNICAL DATA | |
|---|---|
| Rated input voltage | 12 V DC / 24 V DC (SELV / PELV) |
| Input voltage range for charging mode (12 V DC) | Decoupled: 11,9 - 17,4 V DC ±0 % Not decoupled: 11,4 - 17,4 V DC ±0 % |
| Input voltage range for charging mode (24 V DC) | Decoupled: 23,9 - 27 V DC ±0 % Not decoupled: 23,4 - 27 V DC ±0 % |
| Rated input current | 10 A @ (Ue = 24,0 V DC, Ua = 23,2 V DC, Ia = 9,9 A) |
| Switch-on current | ≤35 A / 2 ms |
| Charging current | Max. 7 A; active charging current control |
| Rated input power | 240 W @ (Ue = 24,0 V DC, Ua = 23,2 V DC, Ia = 10 A) |
| GENERAL | |
|---|---|
| Degree of protection | IP20 |
| Overvoltage category | II |
| Pollution degree | 2 |
| Dimensions | 170 × 189 × 147,9 mm | 27,6 kJ (kWs) 172,4 × 116 × 143 mm | 13,4 kJ (kWs) 172,4 × 116 × 143 mm | 5,8 kJ (kWs) |
| Weight | 3,6 kg | 27,6 kJ (kWs) 2,2 kg | 13,4 kJ (kWs) 1,8 kg | 5,8 kJ (kWs) |
| Operating temperature | –40÷60°C |
| Storage temperature | –40÷60°C |
| Relative humidity | ≤95% |
| OUTPUT | |
|---|---|
| Rated output voltage | 12 V DC / 24 V DC |
| Rated output voltage (12 V DC input voltage) | 11,2 V DC ±4 % |
| Rated output current | 10 A |
| Current limiting in buffer mode | 11,25 A ±0,75 A |
| Limit current monitoring in buffer mode through shutdown | 10,3 A ±0,1 A after 1,5 s |
| Energy content (typical) | 27,6 kJ (kWs) @ (Ua = 23,2 V DC, Ia = 2 A) 13,4 kJ (kWs) @ (Ua = 23,2 V DC, Ia = 2 A) 5,8 kJ (kWs) @ (Ua = 23,2 V DC, Ia = 2 A) |
| Efficiency | 95,1 % @ (Ue = 24,0 V DC, Ua = 23,2 V DC, Ia = 10 A) |
| Internal consumption in buffer mode | 1,7 W |
| Short circuit withstand capability | Mains mode: Conditional short-circuit proof Buffer mode: Short-circuit proof |
| Fusing - output | External |
| STANDARD | |
|---|---|
| Total device | 2011/65/EU with 2015/863/EU (RoHS) 1907/2006/EC (REACH) 2009/125/EC (Ecodesign) EN 61010-1 / EN 61010-2-201 / EN 62368-1 UL 508 / C22.2 No. 107.1 |
| EMC | 2014/30/EU (EMC Directive) EN 62040-2 Limit Value Class C1 EN 55011 + A1 Limit Value Class B Group 1 EN 61000-6-2, EN 61000-6-4 |


| PRODUCT CODES | |
|---|---|
| 12.003.00.0000 | DC-UPS Capacitors In.24 Out.24 10A 5,8kJ |
| 12.003.00.0001 | DC-UPS Capacitors In.24 Out.24 10A 13,4kJ |
| 12.003.00.0002 | DC-UPS Capacitors In.24 Out.24 10A 27,6kJ |
| TYPE | DOWNLOADABLE DOCUMENT | DATE |
|---|---|---|
| Datasheet | 27/02/2026 | |
| Wiring diagram | 27/02/2026 | |
| Mechanical drawing | 27/02/2026 |